What is the Importance of Local Breaker Backup LBB Protection in Substation
Why LBB Protection Is Vital for Substation
In this post, we’ll explore the significance of LBB Protection using a practical example of a 220kV substation network. By the end, you’ll understand how LBB protection safeguards against extended faults and potential damage in electrical systems.
If a Relay detects a Fault and operates the Master Trip Relay and still it is not cleared by the Breaker ,rest of the Feeders/Transformers on the concerned Bus will start feeding the Fault.
In this case, the fault will be cleared from the Remote end of these Feeders and the Bus will become dead.
Remote end clearance will result in widespread Disturbance and longer Fault Clearance time.
What Is LBB Protection?
LBB protection is a system designed to act as a backup mechanism when a circuit breaker fails to operate during a fault. Its primary function is to isolate the fault by tripping all breakers connected to the affected bus, ensuring the fault doesn’t escalate and cause widespread damage.
If a breaker fails to clear a fault, the LBB protection activates to quickly isolate the faulted section of the system—typically within an impressive 250 milliseconds. This rapid response prevents prolonged fault duration, which can lead to damage to equipment, snapping of conductors, and extended restoration times.
Why does a circuit breaker fail to open?
A Circuit Breaker may fail to open because of the following reasons:
1. Faulty Contact of Master Trip Relay:
Master Trip Relay has operated, but its Contact is faulty, the Breaker will not Trip.
2. DC Supply of the Breaker has failed.
3. Trip Circuit faulty: There are many elements in the Trip Circuit of the Breaker which may become Faulty.
4. Breaker Mechanism Problem or Breaker stuck up..
What are the Disadvantages of Remote Backup Protection?
1) Longer Fault Clearance time may cause Breaker to explode which may increase the Outage time.
2) In case of Lines, the longer Fault Clearance time may result in Snapping snapping of conductor.
3) In case of Transformer, the longer Fault Clearance time may result in Transformer Failure.
4) Widespread Tripping causes longer restoration time.
To avoid this, we need LBB Protection, which will clear the Fault by Tripping all the Feeders/Transformers connected to the concerned Bus.
What are the Advantages of LBB Protection? Explain with an example.
1) Prevents prolonged fault durations that can damage equipment. Fault will be cleared within 250 ms, hence there will be less damage to the system
2) Reduces the risk of catastrophic transformer failures.
3) Minimizes restoration times, ensuring faster recovery of the electrical network.
4) Enhances overall system reliability and safety.
5) Improved Sensitivity
6) Minimum Network Disruption
Understanding Fault Scenarios Without LBB Protection
Let’s examine a 220kV substation network with five interconnected substations (A, B, C, D, and E). To highlight the importance of LBB protection, we’ll assume that no such protection exists in this setup. Here are three fault scenarios to consider:
All the Line Protection are directed towards the line except Zone 4 which operates for Reverse Direction (for 2 km only).
Similarly for Transformers, all the Protections are directed (Differential and Backup) are directed towards the Transformer.
1. Line Fault (F1):

Lets say there is a Fault , F1 on the Line 1 and its Breaker fails to Trip. Following events take place:
1) Normally for this Fault, Distance Relay will detect the Fault in Zone 1 and issues a command to Master Trip Relay which inturn gives command to the Breaker and the both end Breakers will trip in 30ms.
2) But the Breaker does not Trip (Breaker gets stuck up)
3) Now the Fault is being fed by all the Three Lines Line 2, Line 3 and Line 4.
4) Bus coupler Trips and so the Line 4 does not Trips.
5) Now the Line 2 and Line 3 will Trip from the Remote end on Zone 2 or Backup or Zone 3 depending on the location of the fault.
Now if the LBB Protection was present it would have tripped in 200 ms and also the are of Tripping would be less.
2. Transformer HV Side Fault (F2):

Lets say there is a Fault , F2 on the HV Side of the Transformer No 1 and its Breaker gets stuck up;
1) TFR 1 Differential Relay detects the Fault, but the Breaker does not trip (say Breaker gets stuck up).
2) Now the Fault is being fed by the Lines 1, 2, 3, and 4.
3) Line 4 does not trip as the Bus coupler Breaker trips , before the Line 4 trips.
4) Line 1,2 and 3 trips from the Remote ends as for the remote end, its a Forward direction fault (does not trip from local end as it a reverse direction fault for it)
3. Transformer LV Side (F3) :

Lets say there is a Fault , F3 on the LV Side of the Transformer No 1 and its Breaker gets stuck up.
1) TFR 1 Differential Relay detects the Fault, but the Breaker does not trip (say Breaker gets stuck up).
2) Now the Fault is being fed by the Lines 1, 2, 3, and 4.
3) Line 4 does not trip as the Bus coupler Breaker trips , before the Line 4 trips.
4) Line 1,2 and 3 trips from the Remote ends as for the remote end, its a Forward direction fault (does not trip from local end as it a reverse direction fault for it)
Trip from the Remote end on Backup or Zone 3 depending on the location of the fault.
But due to the Transformer Impedance, the Fault may appear beyond Zone 3.
Or the Fault current may be so small that the Remote end BU fails to detect it.
In this case, the Transformer may feed the Fault current for a longer duration and may result in Transformer Failure.
Conclusion
LBB protection is a cornerstone of modern substation safety, ensuring that faults are addressed swiftly and effectively. Its ability to isolate faults in just 250 milliseconds—compared to the slower response times of backup protection—makes it indispensable for safeguarding transformers, lines, and other critical components. If you’re involved in substation operations or design, investing in robust LBB protection is essential for avoiding costly failures and ensuring long-term reliability.
What are your thoughts on LBB protection? Have you encountered scenarios where it made a significant difference? Share your insights in the comments below, and don’t forget to check back for more Q&A-style posts on electrical engineering topics. Stay connected and stay informed!





